Duct Lagging is typically used to wrap noisy pipes and ducts, and thus help to block the noise contents moving through he pipes. From air flow to liquid content, duct lagging helps to increase sound absorption in the cavity and provides thermal insulation as well.
Types of duct lagging that include a foil-faced reinforced exterior will readily accept a matching lag tape for easy installation. The foil-face also serves as a protective jacket for indoor or outdoor applications. The 2# per sq. foot barrier and the 2″ thick quilted quilted fiberglass absorber improves overall acoustical performance, especially at low frequencies.
1B Lag
PDF Spec Sheet: 1B Duct Lagging
- Nominal Thickness: .090″
- Standard Roll: 48″W x 30’L
- Weight: 1.0 lb. psf
- Temperature Range: -10° to +180° F
- Flammability: UL 94 meets VO FMVSS 302: Pass
- Easy to cut, wrap and install with matching lag tape
Sound Transmission Loss (dB) Octave & Center Frequencies
Product | Octave Band Frequencies (Hz) ASTM E-90 & E 413 | ||||||
---|---|---|---|---|---|---|---|
125 | 250 | 500 | 1K | 2K | 4K | STC | |
1B Lag | 15 | 16 | 21 | 26 | 33 | 38 | 26 |
1B QA-3
Reinforced Foil-Faced Vinyl Barrier Bonded to 1” Scrim Faced Quilted Fiberglass. PDF Spec Sheet: 1B QA-3 Duct Lagging
- Nominal Thickness: 1.0″
- Standard Roll: 48″W x 30’L
- Weight: 1.2 lb. psf
- Temperature Range: -20° to +350° F
- “R” Factor: 4.0
- Flammability – Class A (or 1) Per ASTM E84
- Flammability / Smoke Density: 19.5
- Flammability / Flame Spread: 12.5
- Easy to cut, wrap and install with matching lag tape
Sound Transmission Loss (dB) Octave & Center Frequencies
Product | Octave Band Frequencies (Hz) ASTM E-90 & E 413 | ||||||
---|---|---|---|---|---|---|---|
125 | 250 | 500 | 1K | 2K | 4K | 8K | STC |
1B QA-3 | 18 | 18 | 23 | 30 | 39 | 46 | 29 |
1B QA-9
Reinforced Foil-Faced Vinyl Barrier Bonded to 2” Scrim Faced Quilted Fiberglass. PDF Spec Sheet 1B QA-9 Duct Lagging
- Nominal Thickness: 2.0″
- Standard Roll: 48″W x 30’L
- Weight: 1.4 lb. psf
- Temperature Range: -20° to +200° F
- “R” Factor: 8.0
- Flammability – Class A (or 1) Per ASTM E84
- Flammability / Smoke Density: 19.5
- Flammability / Flame Spread: 12.5
- Easy to cut, wrap and install with matching lag tape
Sound Transmission Loss (dB) Octave & Center Frequencies
Product | Octave Band Frequencies (Hz) ASTM E-90 & E 413 | ||||||
---|---|---|---|---|---|---|---|
125 | 250 | 500 | 1K | 2K | 4K | STC | |
1B QA-9 | 19 | 20 | 23 | 33 | 44 | 53 | 30 |
2B Lag
Reinforced Mylar-Faced Vinyl Barrier PDF Spec Sheet: 2B Duct Lagging
- Nominal Thickness: 1.0″
- Standard Roll: 48″W x 30’L
- Weight: 2.2 lb. psf
- Temperature Range: -20° to +350° F
- “R” Factor: 4.0
- Flammability – Class A (or 1) Per ASTM E84
- Flammability / Smoke Density: 19.5
- Flammability / Flame Spread: 12.5
- Easy to cut, wrap and install with matching lag tape
Sound Transmission Loss (dB) Octave & Center Frequencies
Product | Octave Band Frequencies (Hz) ASTM E-90 & E 413 | ||||||
---|---|---|---|---|---|---|---|
125 | 250 | 500 | 1K | 2K | 4K | STC | |
2B QA-3 | 20 | 23 | 28 | 37 | 48 | 56 | 32 |
2B QA-3
Reinforced Foil-Faced Vinyl Barrier Bonded to 1” Thick Quilted Fiberglass Absorber PDF Spec Sheet: 2B QA-3 Duct Lagging
- Nominal Thickness: 1.0″
- Standard Roll: 48″W x 30’L
- Weight: 2.2 lb. psf
- Temperature Range: -20° to +350° F
- “R” Factor: 4.0
- Flammability – Class A (or 1) Per ASTM E84
- Flammability / Smoke Density: 19.5
- Flammability / Flame Spread: 12.5
- Easy to cut, wrap and install with matching lag tape
Sound Transmission Loss (dB) Octave & Center Frequencies
Product | Octave Band Frequencies (Hz) ASTM E-90 & E 413 | ||||||
---|---|---|---|---|---|---|---|
125 | 250 | 500 | 1K | 2K | 4K | STC | |
2B QA-3 | 20 | 23 | 28 | 37 | 48 | 56 | 32 |
2B QA-9
Reinforced Foil-Faced Vinyl Barrier Bonded to 2” Scrim Faced Quilted Fiberglass. PDF Spec Sheet: 2B QA-9 Duct Lagging
- Nominal Thickness: 2.0″
- Standard Roll: 48″W x 30’L
- Weight: 2.4 lb. psf
- Temperature Range: -20° to +200° F
- “R” Factor: 9.0Flammability – Class A (or 1) Per ASTM E84
- Flammability / Smoke Density: 19.5
- Flammability / Flame Spread: 12.5
- Easy to cut, wrap and install with matching lag tape
- 100% adhesion between barrier and quilt
Sound Transmission Loss (dB) Octave & Center Frequencies
Product | Octave Band Frequencies (Hz) ASTM E-90 & E 413 | ||||||
---|---|---|---|---|---|---|---|
125 | 250 | 500 | 1K | 2K | 4K | STC | |
2B QA-9 | 21 | 24 | 30 | 41 | 54 | 58 | 34 |